13.3ZoneOpons
The Zone Opons select funcons that relate to the operaon of Bypassing, Force Arming and Stay
Arming.
Step 1
Once you have selected a Zone (refertosecon13.1) and Zone Type (refertosecon13.2), you
must select the Zone Opons.
Step 2
To toggle zone opons press the keys 1 to 8, and the corresponding number LED will be lit when
that opon is enabled.
Step 3
Pressing the MENU key ( ) will abort the operaon without saving any changes. Pressing the
ENTER key ( ) will save the opons then loop back to the Zone Selecon procedure so another
zone can be congured. Once all zones have been congured press the MENU key ( ) to perform
other menu acons or the CLEAR key ( ) to exit the menu system.
The available opons are:
Opon 1 - Bypass Allowed
Enabled, the zone can be bypassed. A re zone can never be bypassed regardless of the bypass
seng.
Disabled, zone can not be bypassed.
Opon 2 - Stay Zone
Enabled, the zone is set as a Stay zone. When the system is armed in stay mode this zone will
not generate an alarm.
Disabled, the zone is not a Stay zone.
Opon 3 - Force Zone
Enabled, the zone can be Force Armed when it is not ready to be Armed. A Force Armed zone
will automacally be included in the alarm processing when the zone restores from the not
ready condion.
Disabled, the zone is not able to be Force Armed.
Opon 4, 5, 6, 7 and 8 - Reserved
!
Zone conguraon will not take eect unl the module is next power cycled. This
is because otherwise it is very easy to change a zone seng such that it will then
instantly trigger an alarm and exit the menu mode.